The first priority is to establish the requirements for the particular installation, taking into account the building licensing requirements. It is important to undertake a site-specific risk assessment to ensure that all aspects of the requirements for emergency lighting within the building are catered for. The steps below only cover the basic design considerations for emergency lighting systems.

 

Define building criteria

 

Select system type

i.e. central battery/self contained, duration etc.

 

Select appropriate light source

i e.LED or fluorescent, select luminaire type based on required locations.

Note. BS 5266 specifies that luminaires on stairs must provide direct illuminance onto the stair treads. There must be at least two luminaires within an escape compartment irrespective of size.

 

Illuminance Design

Escape routes

Max. route width = 2m (if wider, treat as multiples).

Minimum of 1 lux min. along centre line plus 0.5 lux over central band covering 50% width of the route.

 

Open areas

Generally greater than 60m2 or as determined by risk assessment: 0.5 lux min (exclude 0.5m band around perimeter wall).

 

High-risk task areas

10% of normal illuminance (no less than 15 lux)

Notwithstanding the above, emergency luminaries shall be located at points of emphasis, such as…

 

Please note, this guidance covers the basic requirements for emergency lighting design, you will need to take into account the building usage requirements and ensure all risk assessments are fully undertaken

 

emergency lighting considerations